Fluke Advanced Geo Earth Ground Tester Kit, 1625-2, 50V, 0.02 to 300 kOhm

747658998451
747658998451
(No reviews yet) Write a Review
All Prices Include VAT
In Stock Ready to Ship
Interested to buy in bulk?
Get customized price
Payment Methods Accepted
Visa Visa
Mastercard Mastercard
Pay Pay
POS Card POS Card
Cash On Delivery Cash On Delivery
Bank Transfer Bank Transfer
SUPPLYVANTAGE
🏅
Original
Products
👍
Warranty
Against Defects
💲
Returns &
Refund Policy
🎧
Dedicated
Support
🛡️
100% Client
Protection
  • Fluke Advanced Geo Earth Ground Tester Kit, 1625-2, 50V, 0.02 to 300 kOhm
  • Fluke Advanced Geo Earth Ground Tester Kit, 1625-2, 50V, 0.02 to 300 kOhm
  • Fluke Advanced Geo Earth Ground Tester Kit, 1625-2, 50V, 0.02 to 300 kOhm
Frequently bought together:

Description

General Specifications

  • Memory: Internal memory storage up to 1500 records accessible via USB port
  • Measuring function: Interference voltage and frequency, earthing resistance 3- and 4-pole with/without clip-on current transformer, resistance 2-pole with AC, 2- and 4-pole with DC
  • Display: 4 digit (2999 Digit) - 7 segment liquid crystal display, with improved visibility
  • Operation: Central rotary switch and function keys

Temperature Range

  • Temperature coefficient: +/-0.1% of reading/Deg.C < 18Deg.C > 28Deg.C
  • Type of protection: IP56 for case, IP40 for battery door according to EN60529
  • Max voltage: Warning – socket "clamp" to socket E, ES, S or H
  • Safety: Protection by double and/or reinforced insulation. Max. 50 V to earth per IEC61010-1. Pollution degree 2
  • Quality standard: Developed, designed and manufactured to comply with DIN ISO 9001
  • External field influence: Complies with DIN 43780 (8/76)
  • Auxiliary power: 6 x 1.5 V alkaline (IEC LR6 or type AA)/li>
  • Battery life span: With IEC LR6/type AA: typ. 3,000 measurements (RE+RH ? 1 kOhm) With IEC LR6/type AA: typ. 6,000 measurements (RE + RH > 10 kOhm)
  • Case material: Polyester
  • Measurement of Interference Voltage DC + AC (UST)
  • limits of error: method: Full wave rectification
  • Measuring range: 1 V to 50 V
  • Display range: 0.0 V to 50 V
  • Resolution: 0.1V
  • Frequency range: DC/AC 45 Hz to 400 Hz sine
  • Accuracy: +/-(5% of rdg + 5 digit)
  • Measuring sequence: Approx. 4 measurements/s
  • Internal resistanc: Approx. 1.5 MOhm
  • Max. overload: Urms = 250V
  • Measurement of Interference Frequency (F)
  • Measuring limits of error: method: Measurement of oscillation period of the interference voltage
  • Measuring range: 6.0 Hz to 400 Hz
  • Display range: 16.0 Hz to 299.9 Hz to 999 Hz
  • Resolution: 0.1 Hz to 1 Hz
  • Range: 1V to 50V
  • Accuracy: +/-(1% of rdg + 2 digit)
  • Earthing Resistance (RE)
  • Measuring method: Current and voltage measurement with probe as IEC61557-5
  • Open circuit voltage: 20/48 V, AC
  • Short circuit current: 250 mA AC
  • Measuring frequency: 94, 105, 111, 128 Hz selected manually or automatic. (AFC) 55 Hz in function R
  • Noise rejection: 120 dB (16 2/3 , 50 , 60, 400 Hz)
  • Max. overload: Urms = 250 V
  • Electrical Measurement Specifications
  • Measuring range: 0.020 Ohm to 300 kOhm
  • Display range: 0.001 Ohm to 2.999 Ohm/3.00 Ohm to 29.99 Ohm/30.0 Ohm to 299.9 Ohm/0.300 kOhm to 2.999 kOhm/3.00 kOhm to 29.99 kOhm/30.0 kOhm to 299.9 kOhm
  • Resolution: 0.001 Ohm/0.01 Ohm/0.1 Ohm/1 Ohm/10 Ohm/100 Ohm
  • Accuracy: +/-(2% of rdg + 2 digit)
  • Operating error: +/-(5% of rdg + 5 digit)
  • Measuring time: Typical 8 seconds with a fixed frequency 30 sec. max. with AFC and complete cycle of all measuring frequencies
  • Additional error because of probe-and auxiliary earth electrode resistance : RH(RS + 2000 Ohm)/RE x 1.25 x 10-6% + 5 digits
  • Measuring error of RH and RS: Typ. 10% of RE + RS + RH
  • Max. probe resistance: ? 1 MOhm
  • Max. auxiliary earth electrode resistance: ? 1 MOhm
  • Automatic Switchover of Measuring Resolution in Dependence to Auxiliary Earth Electrode Resistance RH
  • RH with Umeas = 48 V: < 300 Ohm/< 6 Ohm/< 60 Ohm/< 600 Ohm
  • RH with Umeas = 20 V: < 250 Ohm/< 2.5 kOhm/< 25 kOhm/< 250 kOhm
  • Resolution: 1 mOhm/10 mOhm/100 mOhm/1 Ohm
  • Selective Measurement of the Earthing Resistance (RE Clamp)
  • Measuring method: Current and voltage measurement with probe as per EN61557-5 and current measurement in the individual branch with additional current transformer (patent applied for).
  • Open circuit voltage: 20/48 V AC
  • Short circuit current: 250 mA AC
  • Measuring frequency: 94, 105, 111, 128 Hz selected manually or automatically (AFC), 55 Hz (R1)
  • Noise rejection: 120 dB (162/3, 50, 60, 400 Hz)
  • Max. overload: Max. Urms = 250 V (measurement will not be started)
  • Measuring range: 0.020 Ohm to 300 kOhm
  • Display range: 0.001 Ohm to 2.999 Ohm/3.00 Ohm to 29.99 Ohm/30.0 Ohm to 299.9 Ohm/0.300 kOhm to 2.999 kOhm/3.00 kOhm to 29.99 kOhm
  • Resolution: 0.001 Ohm/0.01 Ohm/0.1 Ohm/1 Ohm/10 Ohm
  • Accuracy: +/-(7% of rdg + 2 digit)
  • Operating error: +/-(10% of rdg + 5 digit)
  • Additional error because of probe- and auxiliary earth typ. electrode resistance: RH(RS + 2000 Ohm)/RETOTAL x 1.25 x 10-6% + 5 digits
  • Measuring error of RH and RS: Typ. of 10% of RETOTAL + RS + RH
  • Measuring time: Typ. 8 sec. with a fixed frequency 30 sec. max. with AFC and complete cycle of all measuring frequencies.
  • Minimal current in single branch to be measured: 0.1 to 0.5mA With transformer
  • Max. interference current through transformer: 3A
  • Resistance Measurement (R~)
  • Measuring method: Current and voltage measurement
  • Measuring voltage: 20VAC, square pulse
  • Short circuit current: > 250 mA AC
  • Measuring frequency: 94, 105, 111, 128 Hz selected manually or automatically (AFC)
  • Measuring range: 0.020 Ohm to 300 kOhm
  • Display range: 0.001 Ohm to 2.999 Ohm/3.00 Ohm to 29.99 Ohm/30.0 Ohm to 299.9 Ohm/300 Ohm to 2999 Ohm/3.00 kOhm to 29.99 kOhm/30.0 kOhm to 299.9 kOhm
  • Resolution: 0.001 Ohm/0.01 Ohm/0.1 Ohm/1 Ohm/10 Ohm/100 Ohm
  • Accuracy: +/-(2% of rdg + 2 digit)
  • Operating error: +/-(5% of rdg + 5 digit)
  • Measuring time: Typical 6 seconds
  • Max. interference voltage: 24 V, with higher voltages measurement will not be started
  • Max overload: Urms max. = 250V
  • Resistance Measurement (R DC)
  • Measuring method: Current- voltage measurement as per IEC61557-4 possible
  • Measuring voltage: 20 VDC
  • Short circuit current: 250 mA DC
  • Formation of measured value: With 4-pole measurement wires on H, S, ES can be extended without additional error. Resistances > 1 Ohm in wire E can cause additional error of 5m Ohm/Ohm.
  • Measuring range: 0.020 Ohm to 300 kOhm
  • Display range: 0.001 Ohm to 2.999 Ohm/3.00 Ohm to 29.99 Ohm/30.0 Ohm to 299.9 Ohm/300 Ohm to 2999 Ohm/3.0 kOhm to 29.99 kOhm/30.0 kOhm to 299.9 kOhm
  • Resolution: 0.001 Ohm/0.01 Ohm/0.1 Ohm/1 Ohm/10 Ohm/100 Ohm
  • Accuracy: +/-(2% of rdg + 2 digit)
  • Operating error: +/-(5% of rdg + 5 digit)
  • Measuring sequence: Approx. 2 measurements/s
  • Measuring time: Typical 4 second including reversal of polarity (2-pole or 4-pole)
  • Maximum interference voltage: ? 3 V AC or DC, with higher voltages measurement will not be started
  • Maximum inductivity: 2 Henry
  • Maximum overload: Urms = 250V
Operating Ambient Temperature (Degree Celsius):
-10 to 50 Deg.C